MA7200-2001-N1,MA7200-2002-N1,MA7200-2003-N1,MA7200-2005-N1,MA7200-2007-N1,MA7200-2010-N1,MA7200-2015-N1,MA7200-2020-N1,MA7200-2025-N1,MA7200-2030-N1,MA7200-2040-N1,MA7200-4001-N1,MA7200-4002-N1,MA7200-4003-N1,MA7200-4005-N1,MA7200-4007-N1,MA7200-4010-N1,MA7200-4015-N1,MA7200-4020-N1,MA7200-4025-N1,MA7200-4030-N1,MA7200-4040-N1,MA7200-4050-N1,MA7200-4060-N1,MA7200-4075-N1;
PA7300系列:
PA7300-2005-N1,PA7300-2010-N1,PA7300-2015-N1,PA7300-2020-N1,PA7300-2025-N1,PA7300-2030-N1,PA7300-2040-N1,PA7300-2050-N1,PA7300-2075-N1,PA7300-2100-N1,PA7300-2125-N1,PA7300-4005-N1,PA7300-4010-N1,PA7300-4015-N1,PA7300-4020-N1,PA7300-4025-N1,PA7300-4030-N1,PA7300-4040-N1,PA7300-4050-N1,PA7300-4075-N1,PA7300-4100-N1,PA7300-4125-N1,PA7300-4150-N1,PA7300-4175-N1,PA7300-4215-N1,PA7300-4250-N1,PA7300-4025-N1,PA7300-4300-N1,PA7300-4350-N1,PA7300-4400-N1,PA7300-4500-N1,PA7300-5005-N1,PA7300-5010-N1,PA7300-5015-N1,PA7300-5020-N1,PA7300-5025-N1,PA7300-5030-N1
東元變頻器導致報過流的可能原因,包括如下幾個方面:
1、真的過電流了;
其中,過電流又分為兩種情況,一種是加速中過流,此時,可以延長一下加速時間,另外,還可以通過調整V/F曲線進行嘗試;另外一種,就是減速中過流,這一般都是減速時間過短引起的,延長一下減速時間就可以了。
2、誤報過電流;
這也可以分為兩種情況:一是機器已經損壞,比方說電流檢測元件,或者是回路中出現了元件損壞,也有可能是輔助電路出現了問題;
二是電磁干擾引起的。這種情況多出現于使用多臺變頻器的場合,或者是變頻器周圍有大的非線性設備的場合,如伺服、中頻爐、高頻爐、開關電源等非線性設備,此時,您需要安裝變頻器輸入端專用濾波器,在諧波含量不是很高的情況下,就可以通過安裝變頻器輸入端專用濾波器來解決